Go top
Paper information

The overvoltage-driven blackout of the Iberian Peninsula on 28th April 2025

L. Rouco, F.M. Echavarren, E. Lobato

Sustainable Energy, Grids and Networks Vol. 45, pp. 102125

Summary:

The Iberian Peninsula blackout on 28th April 2025 occurred due to cascading disconnection of renewable generation with power factor control, triggered by overvoltage generation protections. This paper describes a conceptual model to explain the primary phenomenon that occurred, which we have called an overvoltage-driven blackout. While the phenomenon of voltage collapse, or more precisely undervoltage collapse, is widely discussed in the scientific literature, the phenomenon of an overvoltage-driven blackout is new. An illustrative 3-bus small-scale power system is provided to better understand the evolution of bus voltages in an overvoltage-driven blackout, identifying the critical factors that can lead a power system to a blackout caused by overvoltage. The conceptual model is applied to the state of the Iberian Peninsula electricity system at 12:30 on 28th April 2025, preceding the blackout. The paper will show how, with the loss of renewable generation, the growth of bus voltages exhibits the same pattern as the one identified in the 3-bus small-scale system. A new safety metric (margin to overvoltage-driven blackout) is defined and computed. The paper will demonstrate how the system operated with an insufficient safety margin, leading to an overvoltage-driven blackout, due to a lack of sufficient synchronous reactive power absorption capacity in the central and southern parts of Spain, as well as the low-loaded transmission grid in those regions.


Spanish layman's summary:

Este artículo describe un modelo conceptual para explicar el colapso por sobretensión que provocó el apagón en la Península Ibérica el 28 de abril de 2025. El modelo conceptual se aplica al estado del sistema eléctrico de la Península Ibérica inmediatamente antes del apagón. Se define y calcula el margen de seguridad al colapso por sobretensión.


English layman's summary:

This paper describes a conceptual model to explain the overvoltage-driven blackout of the Iberian Peninsula blackout on 28th April 2025. The conceptual model is applied to the state of the Iberian Peninsula electricity system at 12:30 preceding the blackout. A new safety metric (margin to overvoltage-driven blackout) is defined and computed.


Keywords: Voltage collapse; Voltage control; Ancillary services


JCR-JIF Impact Factor and WoS quartile: 5,700 - Q1 (2025)

DOI reference: DOI icon https://doi.org/10.1016/j.segan.2026.102125

Published on paper: March 2026.

Published on-line: January 2026.



Citation:
L. Rouco, F.M. Echavarren, E. Lobato, "The overvoltage-driven blackout of the Iberian Peninsula on 28th April 2025", Sustainable Energy, Grids and Networks, Vol. 45, pp. 102125, March 2026. [Online: January 2026] doi: 10.1016/j.segan.2026.102125

    Research topics:
  • Steady-state: Load flows, analysis of power system constraints, optimal load flows, voltage control ancilliary service,short-circuits, protections in transmission and ditribution networks
  • Stability: Large disturbance stability, tuning of frequency loadshedding schemes, excitation control, small disturbance stability, tuning of power system stabilizers, identification of AVR and governor models